Section 3.3.3(b) says backflow prevention assemblies must be field tested at least annually. The phrase 'at least' is important. One annual test is the statewide minimum for assemblies in the program, but the public water system, State Water Board, or local health agency may require more frequent testing for a high-hazard premises or an assembly at increased risk of failure.
An annual requirement is not the same thing as a universal December 31 deadline. Water suppliers administer cross-connection control programs, and the customer-facing due date normally comes through the serving utility's notice, portal, or local instructions. Two properties in different water districts can therefore have the same statewide minimum and different paperwork, tester-list, or submission procedures.
The handbook also requires field testing after installation, repair, depressurization for winterizing, or permanent relocation. That means a passing annual test does not cover every later change to the assembly. If the device is repaired or moved, the compliance loop includes another certified field test.
For a property manager, the practical move is to keep a separate record for every assembly. Record its location, serial number, type, serving water supplier, due date, tester, result, repair, retest, and report confirmation. A portfolio with domestic, irrigation, and fire-line assemblies can look compliant while one device is still overdue if everything is tracked only by street address.